Three-phase Reclosers

Three-phase Reclosers

GX Series Recloser

Proven design rated for 10,000 full load operations<br>Polymerinsulation provides industry leading reliability<br>Air insulation for an environmentally friendly design<br>Minimal maintenance required for the high voltage unit<br>Web Human Machine Interface (web HMI) software for field configuration<br>Communication : MODBUS, DNP3.0, DNP3.0,IEC 60870-5-101, IEC 60870-5-104.

Specifications

Pomanique’s GX Series Recloser three-phase, electronically controlled, vacuum-interrupting distribution automation switch provides reliable, economical switching, sectionalizing, advanced metering and automation systems for distribution circuits rated up to 38 kV.

The GX Series Recloser combines solid insulation vacuum interrupters with a reliable, lightweight operating mechanism that utilizes a magnetic actuator to provide a lifetime of trouble-free operation. The solid polymer system does not rely on a gaseous, liquid or foam dielectric. The GX Series Recloser is highly resistant to ozone, oxygen, moisture, contamination and ultraviolet light.

Switch operations are programmed in an electronic control with accurate characteristics and a host of advanced features. When system requirements change, program settings are easily altered with no sacrifice of accuracy or consistency.

Pomanique’s reclosers meet all the requirements for outdoor use in accordance with IEEE C37.60 and IEC 62271-111.

GX recloser

15.5 kV ratings

Model GX15-630-12.5-N GX15-630-16-N GX15-800-12.5-N GX15-800-16-N
Rated continuous current 630 630 800 800
Rated duration of short-circuit 3 3 3 3
Rated short-circuit breaking current 12.5 16 12.5 16
Rated short-circuit making current 31.5 40 31.5 40
Rated lightning impulse withstand voltage 110 110 110 110
Rated short-duration P.F. withstand voltage 50 50 50 50
Impedance μΩ between connections 50 50 50 50
Creepage distance, phase-to-earth 820 820 820 820
Clearance, phase-to-phase 320 320 320 320
Minimum clearance, phase-to-earth 270 270 270 270
Weight 130 130 130 130
Line charging current 2 2 2 2
Cable charging current 10 10 10 10
Max. interrupting time / max. closing time 60 / 60 60 / 60 60 / 60 60 / 60

27 kV ratings

Model GX27-630-12.5-N GX27-630-16-N GX27-800-12.5-N GX27-800-16-N
Rated continuous current 630 630 800 800
Rated duration of short-circuit 3 3 3 3
Rated short-circuit breaking current 12.5 16 12.5 16
Rated short-circuit making current 31.5 40 31.5 40
Rated lightning impulse withstand voltage 125 125 125 125
Rated short-duration P.F. withstand voltage 60 60 60 60
Impedance μΩ between connections 50 50 50 50
Creepage distance, phase-to-earth 820 820 820 820
Clearance, phase-to-phase 320 320 320 320
Minimum clearance, phase-to-earth 270 270 270 270
Weight 140 140 140 140
Line charging current 5 5 5 5
Cable charging current 25 25 25 25
Max. interrupting time / max. closing time 60 / 60 60 / 60 60 / 60 60 / 60

38 kV ratings

Model GX38-630-12.5-N GX38-630-16-N GX38-800-12.5-N GX38-800-16-N
Rated continuous current 630 630 800 800
Rated duration of short-circuit 3 3 3 3
Rated short-circuit breaking current 12.5 16 12.5 16
Rated short-circuit making current 31.5 40 31.5 40
Rated lightning impulse withstand voltage 170 170 170 170
Rated short-duration P.F. withstand voltage 70 70 70 70
Impedance μΩ between connections 50 50 50 50
Creepage distance, phase-to-earth 1250 1250 1250 1250
Clearance, phase-to-phase 320 320 320 320
Minimum clearance, phase-to-earth 350 350 350 350
Weight 150 150 150 150
Line charging current 5 5 5 5
Cable charging current 40 40 40 40
Max. interrupting time / max. closing time 60 / 60 60 / 60 60 / 60 60 / 60

See how orders move from review to dispatch.

Reception, production, testing and shipment areas are organized to keep technical requirements, work progress and delivery records aligned.
Workplace & Customer Reception

Workplace & Customer Reception

Visitors and project teams have a clear place to review requirements, drawings and delivery details before work moves forward.
Organized Production Lines

Organized Production Lines

Defined work areas and orderly material flow help teams keep assemblies, components and order information aligned.
Testing & Verification

Testing & Verification

Routine checks and functional verification are completed against approved requirements before release.
Shipment & Delivery

Shipment & Delivery

Finished orders are checked, protected and organized for traceable handover and coordinated dispatch.

Built for recognised standards

Our documentation package supports project review with internationally recognised safety, quality and environmental marks.

Technical files for your review

Access the latest catalogue, technical parameters and certification files before you finalise your specification.
Go to Download Center

Product questions, answered

Clear guidance on selection, documentation, customization and project delivery.
Please provide the application, system rated voltage and frequency, continuous load current, short-circuit level, insulation level or BIL, and the required operating duty. Also include indoor or outdoor installation, altitude, ambient temperature, pollution level, control voltage, communication requirements, quantity, destination market and applicable standard. A single-line diagram, existing nameplate or project specification will make the review more accurate.
Product Enquiry

Define the right product configuration

Share the application and commercial information available at this stage. Our team will review the request against the product range and identify any details still required for quotation.

Application data

Rated voltage, installation environment and operating duty.

Technical scope

Applicable standard, configuration and required documents.

Delivery planning

Estimated quantity, destination and requested schedule.

Project details

Complete the fields below and include any specification points already confirmed.
询盘表单