Indoor VCB

Indoor VCB

ZN85-40.5

Storage, making and breaking by motor, It can operating by handle.<br>Breaking short-circuit current up to 25kA.<br>Mini motor spring mechanism (about 30W).<br>Installation method: adopt two type installation method.<br>Sealing performance: adopt reliable sealing technical.<br>Incoming & Outgoing method:adopt silicon bushing to make enough insulate distance<br>Safe operating: there is an equipment to protect explosion.

Specifications

ZN85-40.S/T
type indoor high voltage indoor vacuum circuit-breaker is used for switchgear
KYN61-40.5(Z), it is most new type of power supply and distribution equipment.
This product is accordance with GB1984-2003 stand. This series include: Vacuum
circuit breaker truck, isolation truck and fuse truck.

Structural Characteristics

1. This
vacuum circuit breaker adopts compound insulation; it can meet air distance and
creepage under normal run condition, and it effectively reduces the dimension
of VCB, the overall arrangement is reasonable and simple, with aesthetic
appearance.
2. The operating mechanism is especially newly designed for this VCB; the
outlet curve has good adaptation with requirements of vacuum interrupters. It
has high reliable with characteristics of long life and easy maintenance and
free-maintenance for operating mechanism.
3. This truck adopts screw rod nut push-in mechanism which can realize easy
pushing-in or pushing-out of panel; compulsive mechanical interlock way is
adopted; meet the Five Preventions function; suitable for varies site and the
working sites which have rigorous run condition

Ambient Conditions

  1. Ambient temperature: -10℃–+40℃
    2. Relative humidity: daily average 95.monthly average 90.
    3. Earthquake intensity: 8 degree;
    4. Saturated vapor pressure: the average pressure of a day should be no more than
    2.2kPa; the average pressure of a month should be no more than 1.8Kpa;
    5. The height above sea level:≤1000 m (Except special requirements)
    6. Applicable occasions should free from inflammables, explosives, corrosives
    and severe vibration.

Technical Data

Item Unit Value
Rated voltage kV 40.5
Rated frequency Hz 50/60
Rated power frequency withstand voltage(1min) kV 95
Rated lightning impulse withstand voltage(peak) kV 185
Rated current A 630 1250 1600 2000 2500 3150
Rated short circuit breaking current Rated short time withstand stable current 4s rated short time withstand current kA 25 25 25
31.5 31.5 31.5 31.5 31.5
Rated short circuit closing current(peak) Rated peak withstand current Rated dynamic stable current kA 63 63 63
80 80 80 80 80
Breaking times of short circuit breaking current times 20
Rated thermal stability time s 4
Rated operating sequence O-0.3s-CO-180s-CO
Mechanical life times 10000
Rated operating voltage V DC110/220 AC110/220

See how orders move from review to dispatch.

Reception, production, testing and shipment areas are organized to keep technical requirements, work progress and delivery records aligned.
Workplace & Customer Reception

Workplace & Customer Reception

Visitors and project teams have a clear place to review requirements, drawings and delivery details before work moves forward.
Organized Production Lines

Organized Production Lines

Defined work areas and orderly material flow help teams keep assemblies, components and order information aligned.
Testing & Verification

Testing & Verification

Routine checks and functional verification are completed against approved requirements before release.
Shipment & Delivery

Shipment & Delivery

Finished orders are checked, protected and organized for traceable handover and coordinated dispatch.

Built for recognised standards

Our documentation package supports project review with internationally recognised safety, quality and environmental marks.

Technical files for your review

Access the latest catalogue, technical parameters and certification files before you finalise your specification.
Go to Download Center

Product questions, answered

Clear guidance on selection, documentation, customization and project delivery.
Please provide the application, system rated voltage and frequency, continuous load current, short-circuit level, insulation level or BIL, and the required operating duty. Also include indoor or outdoor installation, altitude, ambient temperature, pollution level, control voltage, communication requirements, quantity, destination market and applicable standard. A single-line diagram, existing nameplate or project specification will make the review more accurate.
Product Enquiry

Define the right product configuration

Share the application and commercial information available at this stage. Our team will review the request against the product range and identify any details still required for quotation.

Application data

Rated voltage, installation environment and operating duty.

Technical scope

Applicable standard, configuration and required documents.

Delivery planning

Estimated quantity, destination and requested schedule.

Project details

Complete the fields below and include any specification points already confirmed.
询盘表单